X2 pro 7 with 2 Ethernet

7'' HMI with iX runtime

  • 800 × 480 pixel (16:9)
  • TFT-LCD touch screen
  • 1.5 GB application memory
  • Ethernet 2x100 Mbit
  • -10°C to +60°C operating temperature
  • CE, FCC, KCC, UL approvals
  • DNV GL, KR, LR, ABS, CCS, BV, NK, RS marine approvals
Contact Print (PDF)

Facts

General description

Part number 630009405
Life cycle status Active
Warranty 2 year

Certifications

General CE, FCC, KCC
Marine KR, LR, ABS, BV, CCS, NK, DNV GL, RS
Safety UL 61010-1, UL 61010-2-201, CAN/CSA-C22.2 No. 61010-1, CAN/CSA-C22.2 No. 61010-2-201

Mechanical

Mechanical size 204 x 143 x 50mm
Mounting option Panel Mount, VESA 75 x 75
Number of touches 1million finger touch operations
Touch type Resistive
Cut-out size 189 x 128mm
Weight 0.8 kg
Housing material Powder-coated aluminum, Gray

Power

Input voltage 24 V DC (18 to 32 VDC)CE: The power supply must conformwith the requirements according to IEC 60950 and IEC 61558-2-4.UL and cUL: The power supplymust conformwith the requirements for class II power supplies.
Power consumption (max) 14.4W
Input fuse Internal DC fuse

System

Hardware platform X2
CPU i.MX6DualLite, Dual Cortex-A9 1.0GHz 512kBL2cache
RAM 1 GB
FLASH 2GB SSD(eMMC), 1.5GB free for application

Display

Size diagonal 7" diagonal
Resolution 800x480 pixels
Backlight LED Backlight
Backlight life time 20000 hours
Backlight brightness 350 cd/m2
Backlight dimming Industrial Dimming
Display type TFT-LCD with LED backlight

Serial communication

Number of serial ports 1 Port 9pin DSUB
Serial port 1 RS 232 (RTS/CTS)
Serial port 2 RS422/485
Serial port 3 RS485 (only if COM 2 is RS485)

Ethernet communication

Number of Ethernet ports 2
Ethernet port 1 1x10/100 Base-T (shielded RJ45)
Ethernet port 2 1x10/100 Base-T (shielded RJ45)

Communication CAN

Number of CAN ports 1
CAN port 1 0.5 MBit

Expansion interface

Expansion port Yes, ciX expansion module
SD card SD and SDHC
USB 1xUSB 2.0 500mA

Environmental

Operating temperature -10°C to +60°C
Storage temperature -20°C to +70°C
Shock 15g, half-sine, 11ms according to IEC60068-2-27
Vibration 1g, according to IEC 60068-2-6, Test Fc
Sealing front IP65, NEMA 4X/ 12 and UL 50E Type 4X/ 12
Sealing back IP20
Humidity 5% – 85% non-condensed
Altitude (max) < 3000m

Resources

Drawings

File name Date
Cable CAB113: Cable for ModBus RS485 between X2 panel and BFI 2022-10-05 14:15:53
CAB108 Cable Drawing for X2 base, X2 pro, X2 marine, X2 control, X2 motion, iX Panel TxA/B/C iX operator panel 2022-09-20 15:55:15
CAB105 Cable Drawing for X2 base, X2 pro, X2 marine, X2 control, X2 motion, iX Panel TxA/B/C operator panel 2022-10-10 08:36:51
CAB106 Cable Drawing for X2 base, X2 pro, X2 marine, X2 control, X2 motion, iX Panel TxA/B/C operator panel 2022-09-20 15:58:03
CAB107, 25-pol to 9-pol adapter, Cable Drawing for X2 base, X2 pro, X2 marine, X2 control, iX Panel TxA/B/C operator panel 2022-09-20 15:57:58
CAB110 Cable Drawing for X2 pro, X2 marine, X2 control, X2 motion, iX Panel TxA/B/C operator panel 2022-09-20 15:57:35
CAB109 Cable Drawing for X2 base, X2 pro, X2 marine, X2 control, X2 motion, iX Panel TxA/B/C iX operator panel 2022-09-20 15:58:14
CAB153 Cable Drawing for X2 base, X2 pro, X2 marine, X2 control, X2 motion, iX Panel TxA/B/C operator panel 2022-10-10 08:38:06
CAB150 Cable Drawing for X2 base, X2 pro, X2 marine, X2 control, iX Panel TxA/B/C operator panel 2022-10-10 08:37:51
CAB104 Cable Drawing forX2 base, X2 pro, X2 marine, X2 control, X2 motion, iX Panel TxA/B/C operator panel 2022-10-10 08:36:52
CAB103 Cable Drawing for X2 base, X2 pro, X2 marine, X2 control, X2 motion, iX Panel TxA/B/C 2022-10-10 08:36:50
CAB101 Cable Drawing for X2 pro, X2 marine, X2 control, X2 motion, iX Panel TxA/B/C operator panel 2022-10-10 08:36:49
CAB100 Cable Drawing for X2 pro, X2 marine, X2 control, X2 motion, iX Panel TxA/B/C operator panel 2022-09-20 15:57:40
​​Outline drawing, X2 pro 7, X2 marine 7, X2 control 7, X2 motion 7 2022-09-22 08:20:11
​​Cutout drawing, X2 pro 7, X2 marine 7, X2 control 7, X2 motion 7 2022-09-22 08:27:01
​​3D drawing, X2 pro 7, X2 marine 7, X2 control 7, X2 motion 7 in STEP format 2022-09-22 08:47:40

Information document

File name Date
​Guidelines for TxA and TxB migration to X2. 2022-10-10 08:38:10

Configuration files

File name Date
EDS file for CiX-CAN and X2 2022-09-28 13:38:21
GSD files for CiX-DP Profibus module 2022-10-10 08:34:45

Brochures

File name Date
X2 series (German) 2022-09-21 08:11:38
X2 brochure (Spanish)​ 2022-09-21 08:12:32
X2 brochure 2019 (French) 2024-01-15 10:52:15
X2 brochure (English), BREN631 2022-09-21 08:11:56
Limited availability

X2 pro 7 with 2 Ethernet

7'' HMI with iX runtime


EOL - End Of Life:
-

LTB - Last Time Buy:
-

LTD - Last Time Delivery:
-

LTR - Last Time Repair:
-

Replacement Parts: